Fire Tests on Window Assemblies Protected by Automatic Sprinklers
Författare
Oleszkiewcz I, Richardson J K
Utgivare
National Fire Protection Association (NFPA)
Utgivningsår
1987-05
Full scale fire tests on wired and tempered glazing in steel and aluminimum frames are described. These assemblies achieved fire resistance ratings when exposed to a standard fire of 45 min to 2 h. The maximum radiant heat flux transmitted through the glass was reduced by more than 90%.
Titel: |
Fire Tests on Window Assemblies Protected by Automatic Sprinklers |
Författare: |
|
Utgivare:
|
|
Utgivningsår:
|
1987-05
|
Omfång:
|
18 s
|
Serie:
|
Fire Technology
|
Klassificering:
|
|
Nyckelord:
|
|
Serie nr:
|
Nr 2/1987
|