On the Evaporation Effect of a Sprinkler Water Spray
Författare
Chow W K
Utgivare
National Fire Protection Association (NFPA)
Utgivningsår
1989-11
A crude model for estimating the evaporation heat loss due to a sprinkler water spray in a smoke layer is reported.
It is found that the evaporation heat loss lies below 11.2% of the convective loss when water travels through a hot gas layer 0.9 m thick and 60 C under normal sprinkler operating conditions. It is also found that the value may go up to 26% if the smoke layer reaches 1.5 m and 273 C.
Titel: |
On the Evaporation Effect of a Sprinkler Water Spray |
Författare: |
|
Utgivare:
|
|
Utgivningsår:
|
1989-11
|
Omfång:
|
10 s
|
Serie:
|
Fire Technology
|
Klassificering:
|
|
Nyckelord:
|
|
Serie nr:
|
Vol 25, No 4, Nov 1989
|